What it is
Deflection describes how much a foundation bends. The ASCE Texas Section guidelines define the deflection ratio as the maximum deviation of a point from a straight line drawn between two other points, divided by the distance between them, written as a fraction of L, the span. Tilt describes how much the foundation leans overall, expressed as a percentage: the difference in elevation over the distance.
The numbers
For deflection, the guidelines use L/360 as an analogous limit, borrowed from the International Residential Code's limit on floor deflection under live load. Their reasoning: if measured deflection is under L/360, the foundation is unlikely to be materially deflected unless visible signs show otherwise; if it exceeds L/360 and there are sufficient symptoms, an engineer will generally be justified in concluding that deflection is excessive.
For tilt, the guidelines note that a tilt greater than 1 percent is usually noticeable to occupants, and that the Americans with Disabilities Act considers a 2 percent slope too large. For overall structural tilt, an engineer can also check stability using the veneer-panel criterion from the International Existing Building Code.
Why they are not pass marks
The guidelines are careful to require symptoms alongside numbers. A deflection beyond L/360 with no cracking, binding doors or other distress may reflect how the house was built rather than how it has moved. A deflection under L/360 with significant symptoms still deserves attention. The guidelines also caution engineers about short spans: over distances under about 20 feet, built-in unevenness can dominate the measurement, so a steep reading between two nearby points may mean little.
Engineers therefore weigh measurements together with brick coursing, door alignment, crack patterns, floor coverings and history. Two competent engineers can reach different conclusions about the same readings, and good reports explain their reasoning.
How a buyer uses this
When an engineer's report cites L/360 or tilt percentages, look for three things: which points were used, whether the engineer adjusted for floor coverings, and which symptoms supported the conclusion. A report that lists numbers without connecting them to observed distress is harder to rely on.
Who decides
Licensed professional engineers apply these criteria. A Texas home inspector forms a performance opinion from visible indications and is not required to measure elevations.
Common misreadings
"Anything over L/360 needs piers." The guidelines call for sufficient symptoms too.
"Under 1 percent tilt means no problem." Tilt and deflection are separate questions.
"Short-span readings show damage." Built-in unevenness dominates under about 20 feet.
Field notes
If two engineers disagree, ask each to explain which readings and symptoms drove the conclusion. Disagreement often comes down to how built-in unevenness was treated.
Why numbers need symptoms
Two houses can show identical deflection numbers and be in very different condition. One may have been built slightly out of level and never moved; the other may have moved recently and be cracking. The guidelines therefore pair every calculation with observed distress before an engineer concludes that deflection is excessive. For a buyer, that means a survey report full of numbers but silent on what the engineer saw in the walls, doors and brick is only half a report.
Where the facts come from
ASCE Texas Section, Guidelines for the Evaluation and Repair of Residential Foundations, Version 3 (2022); Foundation Performance Association discussion of the history of Texas performance criteria.